CyberPower Systems Online S Series Double Conversion 10000VA Tower UPS with LCD
CyberPower OLS10000E?is a high-performance UPS featuring online double-conversion topology, which provides seamless Pure Sine Wave power for mission-critical devices such as NAS and servers, DVRs/surveillance systems, transportation and infrastructure, and emergency systems. It?s typically integrated in the back office, server room, and data center environment. Selected product is equipped with a Maintenance Bypass Switch. By flipping the switch, the power supply is safely transferred to utility. This allows service personnel to carry out fast on-site maintenance without having to shut down any connected equipment.
FEATURES
- Online (Double Conversion) UPS Topology
- Energy Saving Technology
- UPS Parallel Expansion
- Generator Compatible
- Overload Protection
- Maintenance Bypass Switch
- Zero Transfer Time
- Smart Battery Management (SBM)
- External Battery Module (EBM)
- Surge and Spike Protection
- EMI and RFI Filtration
- LCD Status Display
- Emergency Power Off (EPO) Port
- PowerPanel® Management Software
- SNMP/ HTTP Remote Management Capability
- Tower Form Factor
GENERAL
UPS Topology
Online Double Conversion |
Energy Saving Technology
Online ECO Mode Efficiency > 96% |
Active PFC Compatibility
Yes |
Parallel Expansion (Max. Units)
4 |
INPUT
Generator Compatibility
Yes |
Nominal Input Voltage (Vac)
230 |
Input Voltage Range (Vac)
110 ~ 276 |
Adjustable Voltage Range (Vac)
0~80% Load for 110 ~ 276 Vac |
0~100% Load for 176 ~ 276 Vac |
Input Frequency (Hz)
50 ± 5 |
60 ± 6 |
Input Frequency Detection
Auto-sensing |
Rated Input Current (A)
45.5 |
Input Power Factor
0.99 |
Input Connector Type
Hardwire Terminal Block |
OUTPUT
Capacity (VA)
10000 |
Capacity (Watts)
9000 |
On Battery Waveform
Pure Sine Wave |
On Battery Voltage(s) (Vac)
208 ± 1% |
220 ± 1% |
230 ± 1% |
240 ± 1% |
Output Voltage Setting
Configurable |
On Battery Frequency (Hz)
50 ± 0.1% |
60 ± 0.1% |
Output Frequency Setting
Configurable |
ECO Mode Voltage Tolerance
± 10 % |
± 15 % |
Overload Protection
Internal Current Limiting , Circuit Breaker , Fuse |
Overload Protection (Line Mode)
105~125% Load for 10 min, 125~150% Load for 1 min, 150~170% Load for 10 sec, >170% Load for 1 sec |
Overload Protection (Battery Mode)
105~125% Load for 2 min, 125~150% Load for 30 sec, >150% Load for 1 sec |
Overload Protection (Bypass Mode)
125~150% Load for 1 min, 150~170% Load for 10 sec, >170% Load for 1 sec |
Crest Factor
3 : 1 |
Harmonic Distortion (Linear Load)
THD?2% |
Harmonic Distortion (Non-linear Load)
THD?5% |
Internal Bypass
Automatic Bypass |
Maintenance Bypass
Yes |
Outlets - Total (Socket)
1 |
Outlet Type (Socket)
Hardwire Terminal Block x 1 |
Outlets - Battery & Surge Protected(Socket)
1 |
Typical Transfer Time (ms)
0 |
BATTERY
Runtime at Half Load (min)
11 |
Runtime at Full Load (min)
4 |
Typical Recharge Time (Hours)
7 |
Maximum Charging Current (A)
1 |
Start On Battery
Yes |
Smart Battery Management (SBM)
Yes |
User Replaceable
No |
Battery Type
Sealed Lead-acid |
Single Battery Capacity (AH)
12 V 9 AH |
External Battery Module (EBM)
BPSE240V47AOA |
Max. EBM Quantity
15 |
SURGE PROTECTION & FILTERING
Surge Suppression (Joules)
445 |
EMI/RFI Filtration
Yes |
MANAGEMENT & COMMUNICATIONS
LCD Panel
Yes |
LCD Information Display
Operation Type , Power Status , Battery Status , Load Status , Fault & Warning , Other Information , Event & Log |
LCD Setting & Control
Mode Setting , Alarm Setting , Input & Output , Battery Setting , Fault & Warning |
LED Indicators
Line Mode , Battery Mode , Bypass Mode , UPS Fault |
HID Compliant USB Port (pcs)
1 |
Serial Port
RS232 |
Dry Contact (with Relay)
Optional |
Emergency Power Off (EPO) Port
Yes |
Audible Alarms
Battery Mode , Low Battery , Overload , Overcharge , Overheat , UPS Fault |
Power Management Software
PowerPanel® Business Edition |
SNMP / HTTP Remote Monitoring
Yes - with optional RMCARD20x |
PHYSICAL
Form Factor
Tower |
Enclosure Construction
Metal |
Color
Black |
PHYSICAL SIZE - UPS MODULE
Dimensions (WxHxD) (mm.)
260 x 708 x 550 |
Weight (kg.)
86 |
PHYSICAL SIZE - BATTERY MODULE
Dimensions (WxHxD)
260 x 718 x 550 |
Weight (kg.)
116 |
SHIPPING DIMENSIONS
Dimensions (WxHxD) (mm.)
428 x 970 x 720 |
Weight (kg.)
98 |
ENVIRONMENTAL
Operating Temperature (°C)
0 ~ 40 |
Operating Relative Humidity (Non-condensing) (%)
0 ~ 90 |
Operating Elevation (feet/meters)
?1000 Load Derated 1% per 100m from 1000m and 2000m |
Storage Temperature (°C)
-15 ~ 45 |
Storage Relative Humidity (Non-condensing) (%)
0 ~ 95 |
Online Thermal Dissipation (BTU/hr)
2672 |
CERTIFICATIONS
Certifications
CE |
RoHS
Yes |
WARRANTY
Additional information
Application | Corporate & Enterprise, Servers |
---|---|
BrandName | CyberPower |