The OLS2000E features remote network management capabilities which include the PowerPanel® Business Edition software, an optional SNMP/ HTTP remote management card, and an optional ENVIROSENSOR. These management tools enable administrators to perform various operations including remote management, real-time monitoring, UPS configuration, and scheduled server/workstations shutdowns. All Smart App UPS systems and Remote Management Card have achieved the status of Cisco EnergyWise certified, better supporting other EnergyWise-enabled entities and be easily monitored and controlled to achieve the best energy performance under the EnergyWise operation framework.
General
|
 |
UPS Topology |
Double-Conversion |
Energy Saving |
ECO Mode Efficiency > 95% |
Active PFC Compatible |
Yes |
|
|
Input
|
 |
Voltage |
230Vac |
Input Voltage Range |
160Vac - 300Vac |
Adjustable Voltage Range |
110Vac - 300Vac |
Input Frequency Range |
40Hz - 70Hz |
Rated Input current |
16A |
Input Power Factor |
?0.98 |
Cold Start |
Yes |
Backfeed Protection |
Yes |
Plug Type |
IEC C20 |
Plug Style |
right |
Input Current (Amp) |
16A |
Cord Length (ft.) |
6 |
Cord Length (m) |
1.8 |
|
|
Output
|
 |
VA |
2000 |
Watts |
1800 |
On Battery Waveform |
Sine Wave |
On Battery Voltage |
208, 220, 230, 240Vac (Configurable) |
Automatic Voltage Regulation (Line Mode) |
± 1% |
On Battery Frequency |
50/60Hz ± 0.5% (Auto-Sensing or Configurable) |
Overload Protection |
AC Mode: Warning only @ 110%>Load>105%, Transfer to bypass after 60sec @ 120%>Load>110%, Transfer to bypass immediately@ Load>120ºttery Mode: Warning only @ 110%>Load>105%, Shutdown after 10sec @ 120%>Load>110%, Shutdown immediately @ Load>120% |
Outlets - Total |
5 |
Outlet Type |
(2 2) IEC320 C13, (1) Terminal Block |
Outlets - Battery & Surge Protected |
5 |
Outlets - Critical Load |
5 |
Rated Power Factor |
0.9 |
Crest Factor |
3:1 |
Harmonic Distortion |
THD < 3% at Linear Load, < 5% at Non-linear Load |
ECO Mode Voltage Regulation |
± 10%, ± 15% ,± 20% (Configurable) |
Bypass |
Internal Bypass (Automatic and Manual) |
Transfer Time |
0ms |
|
|
Battery
|
 |
Runtime at Half Load (min) |
16 |
Runtime at Full Load (min) |
6 |
Battery Type |
Sealed Lead-Acid |
Battery Number |
1228WS |
Battery Size |
12V/7AH |
Battery Quantity |
6 |
Typical Recharge Time |
5 Hours |
Smart Battery Management (SBM) Mode |
Yes |
Extended Battery Module |
BPSE72V45A |
|
|
Surge Protection & Filtering
|
 |
Surge Suppression |
440 Joules |
Phone Protection RJ11 |
Yes |
Phone / Network Protection RJ11/RJ45 |
1-In, 1-Out |
EMI/RFI Filtration |
Yes |
|
|
Management & Communications
|
 |
LCD Control Panel |
Yes |
Multifunction LCD Diagnostic Display |
22 different status options via the UPS Information menu and Event Log menu |
HID Compliant USB Port |
Yes |
Serial Port |
Yes |
Emergency Power Off (EPO) Port |
Yes |
Management Cable |
USB Cable, Serial Cable, Phone Cable |
Audible Alarms |
Yes |
Software |
PowerPanel® Business Edition |
SNMP / HTTP Remote Monitoring |
Yes, with optional RMCARD302 / RMCARD303 |
|
|
Physical
|
 |
Form Factor |
Tower |
Enclosure Construction |
Steel |
|
|
Physical - UPS Module
|
 |
Dimensions (WxHxD) (in.) |
7.72 x 12.27 x 16.38 |
Dimensions (WxHxD) (mm.) |
196 x 337 x 416 |
Weight (kg.) |
23.8 |
|
|
Physical - Battery Module
|
 |
Dimensions (WxHxD) (in.) |
7.72 x 12.27 x 16.38 |
Dimensions (WxHxD) (mm.) |
196 x 337 x 416 |
Weight (kg.) |
34.2 |
|
|
Environmental
|
 |
Operating Temperature |
32 °F to 104 °F / 0 °C to 40 °C |
Operating Humidity |
20% ~ 90% non-condensing |
Operating Elevation |
0-5000 feet (0-1500 meters) |
Storage Temperature |
-4 °F to 122 °F / -20 °C to 50 °C |
Storage Relative Humidity |
10% to 90% |
Storage Elevation |
0-5000 feet (0-1500 meters) |
Online Thermal Dissipation |
666 BTU/hr |
Audible noise at 1.5M from surface of unit |
45dBA |
|
|
Certifications
|
 |
Certifications |
CE, Gost-R |
RoHS |
RoHS Compliant |
|
|
Ã
Warranty
|
 |
Product Warranty |
2 Years Limited |
Connected Equipment Guarantee |
Lifetime |
CEG Amount |
100000 AUD |
|